Carrier reefer container: Alarm 15 "Loss of cooling", no ice on evaporator
EL-0035 · Solved · rating 0 · works for 0 engineers · occurred 18 May 2018
Source: /cases/el-0035
Symptoms#
- Reefer container found with Alarm 15 "Loss of cooling".
- It felt like something was blocking the air flow.
- When warm water was poured over the evaporator, nothing came out of the drain tube.
Checked#
| Check | Result |
|---|---|
| Evaporator coil | No ice |
| Evaporator fans | Turn in the correct direction |
| Suction / discharge pressure | 0.7 / 11.2 bar |
| Suction temperature | −26 °C |
Diagnosis#
The air duct was frozen solid, right down to the bottom. Ice blocked the air flow.
Fix#
- Warmed up the cover of the supply air sensors.
- Poured water in there to clear the ice.
Result#
The unit started cooling again.