Aalborg boilers: local panels go offline, fan trips at ignition
EL-0040 · Solved · rating 0 · works for 0 engineers · occurred 10 Nov 2020
Source: /cases/el-0040
Symptoms#
- Two boilers, one ECR PC. First the boiler 1 local panel went offline now and then; a reset helped for a day.
- Then the boiler 2 local panel went offline, flashing online / offline, and did not reset. In the LAN tab one panel ID was missing.
- The local panels also glitched with the PC switched off, so the PC was not the cause.
- In auto, the fan of boiler 1 tripped at ignition (start fail or overload). In manual everything worked.
Checked#
| Check | Result |
|---|---|
| Restart of PC, hub and panel | No change |
| LAN cables reconnected and wiggled | No alarm — not vibration or a loose cable |
| Unisab board in the main (common) panel | Replaced — worse, both boilers red on the PC |
| Reinstall of the PC software from USB | Failed with an error |
Diagnosis#
The Unisab board in the local panel of boiler 2 had failed.
The LAN goes in a chain: Adam box (hub) → boiler 2 local panel → power panel → boiler 1 local panel. The bad board in boiler 2 also cut off the panels after it, so the boiler 1 fan tripped although boiler 1 had no fault.
Fix#
- Replaced the Unisab board in the boiler 2 local panel (about 3–4 hours of work).
- The USB software key had been put back in a different USB port during the work. The PC program ran in demo mode for two hours, then crashed. Moved the key back to its original port and restarted the PC.
Result#
All panels online. The fan trip on boiler 1 stopped.
Comments · 0
No comments yet.