Aalborg boilers: local panels go offline, fan trips at ignition

BoilerAutomation / PLCAalborg

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Two boilers, one ECR PC. First the boiler 1 local panel went offline now and then; a reset helped for a day.
  • Then the boiler 2 local panel went offline, flashing online / offline, and did not reset. In the LAN tab one panel ID was missing.
  • The local panels also glitched with the PC switched off, so the PC was not the cause.
  • In auto, the fan of boiler 1 tripped at ignition (start fail or overload). In manual everything worked.

Checked#

CheckResult
Restart of PC, hub and panelNo change
LAN cables reconnected and wiggledNo alarm — not vibration or a loose cable
Unisab board in the main (common) panelReplaced — worse, both boilers red on the PC
Reinstall of the PC software from USBFailed with an error

Diagnosis#

The Unisab board in the local panel of boiler 2 had failed.

The LAN goes in a chain: Adam box (hub) → boiler 2 local panel → power panel → boiler 1 local panel. The bad board in boiler 2 also cut off the panels after it, so the boiler 1 fan tripped although boiler 1 had no fault.

Fix#

  1. Replaced the Unisab board in the boiler 2 local panel (about 3–4 hours of work).
  2. The USB software key had been put back in a different USB port during the work. The PC program ran in demo mode for two hours, then crashed. Moved the key back to its original port and restarted the PC.

Result#

All panels online. The fan trip on boiler 1 stopped.