Boll & Kirch filter turns back to the dirty chamber at flushing

OtherBoll & Kirch 6.72, BK 2200 controller

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Comments · 0

Symptoms#

At backflushing:

  1. The solenoid worked and the filter turned to the clean chamber.
  2. The solenoid switched off, air was cut, and the filter turned back to the dirty chamber.
  3. This happened twice in a row.
  4. After the second time it stayed on the dirty chamber, and the second (flushing) solenoid flushed the clean one.

Checked#

CheckResult
Solenoids, fusesOK
Filter elementsChanged — no change
Solenoid valve (without coil)Changed — no change
Limit switchSwapped, and jumpered at the closing moment — no change
Main controller boardChanged with a spare — same symptoms
BK 2200 controller board — replacing it did not help
BK 2200 controller board — replacing it did not help

Diagnosis#

When changing over from heavy fuel to diesel, the flushing interval was changed from 1 hour to 2 hours. The filter type setting is in the next menu, and it was changed by mistake: 6.64 (the next value in the list) instead of the correct 6.72. With the wrong filter type, the controller ran a different sequence.

Fix#

Set the filter type back to 6.72 in the controller menu.