Boll & Kirch filter turns back to the dirty chamber at flushing
EL-0041 · Solved · rating 0 · works for 0 engineers · occurred 25 Nov 2020
Source: /cases/el-0041
Symptoms#
At backflushing:
- The solenoid worked and the filter turned to the clean chamber.
- The solenoid switched off, air was cut, and the filter turned back to the dirty chamber.
- This happened twice in a row.
- After the second time it stayed on the dirty chamber, and the second (flushing) solenoid flushed the clean one.
Checked#
| Check | Result |
|---|---|
| Solenoids, fuses | OK |
| Filter elements | Changed — no change |
| Solenoid valve (without coil) | Changed — no change |
| Limit switch | Swapped, and jumpered at the closing moment — no change |
| Main controller board | Changed with a spare — same symptoms |
Diagnosis#
When changing over from heavy fuel to diesel, the flushing interval was changed from 1 hour to 2 hours. The filter type setting is in the next menu, and it was changed by mistake: 6.64 (the next value in the list) instead of the correct 6.72. With the wrong filter type, the controller ran a different sequence.
Fix#
Set the filter type back to 6.72 in the controller menu.