Symptoms#

  • After drydock the boiler water level DP transmitter stopped showing the right level. The reading made no sense.
  • Before drydock it worked. Nobody said they had touched it.

Checked#

CheckResult
Power off and restartNo change
Output current measuredReading still wrong

A new transmitter was nearly ordered.

Diagnosis#

The equalising valve on the transmitter valve manifold had been opened during the drydock repair, and it was left open.

DP level transmitter unit: the equalising valve is on the valve manifold, between the two connection valves
DP level transmitter unit: the equalising valve is on the valve manifold, between the two connection valves

Fix#

Closed the equalising valve.

Result#

The transmitter showed the correct level at once.