Boiler water level DP transmitter shows a wrong level after drydock
EL-0053 · Solved · rating 0 · works for 0 engineers · occurred 12 May 2022
Source: /cases/el-0053
Symptoms#
- After drydock the boiler water level DP transmitter stopped showing the right level. The reading made no sense.
- Before drydock it worked. Nobody said they had touched it.
Checked#
| Check | Result |
|---|---|
| Power off and restart | No change |
| Output current measured | Reading still wrong |
A new transmitter was nearly ordered.
Diagnosis#
The equalising valve on the transmitter valve manifold had been opened during the drydock repair, and it was left open.
Fix#
Closed the equalising valve.
Result#
The transmitter showed the correct level at once.