HFO transfer pump: start relay chatters, pump will not start in manual

PumpsElectrical

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Comments · 0

Symptoms#

  • When Start is pressed, relay 4 in the starter crackles and buzzes. The main contactor does not pull in.
  • The main contactor is new.
  • With one output wire of the control circuit disconnected, the pump starts and self-holds normally.
  • The pump had worked a month before. Nothing had been changed.
  • The control system showed the tank as empty.

Checked#

  • Start push button, Manual/Auto switch and their wiring: continuity OK.

Diagnosis#

The tank was in fact full. Nobody had sounded it; the level was only read on the computer.

On this starter the auto stop level switch (LS) stops the pump also in Manual mode:

  • Pressing Start closed relay 4. Its contacts dropped relay 5.
  • The level switch at once closed relay 5 again.
  • While Start was held, the two relays opened and closed about once a second. This was the crackling.
Control circuit: Manual/Auto switch, relays 4 and 5, auto start and auto stop level switches (LS)
Control circuit: Manual/Auto switch, relays 4 and 5, auto start and auto stop level switches (LS)

Fix#

No repair was needed. The tank was sounded and found full. The starter has no fault.