AC compressor loses oil pressure at start after overhaul with new parts

Refrigeration & HVACLow oil pressure

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The air-conditioning compressors were overhauled with a new spare parts kit.
  • After the overhaul, oil pressure dropped at every start.

Checked#

  • The oil pressure sensor was replaced several times — no change.
  • The compressor was opened and rebuilt several times.

Diagnosis#

The new valve plates from the kit had two more holes than the old ones. They looked the same at first sight. It was found only on about the fifth attempt.

Fix#

Fitted the old valve plates back.

Result#

Oil pressure at start was normal again.