SAM Electronics ME HT cooling: temperature swings 8 °C in auto

Main EngineAutomation / PLCSAM Electronics

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The ME HT cooling water temperature controller (HT cooler valve) could not hold the set point in auto. The temperature went up and down by about 8 °C.
  • Because of this, the system was run in manual for about a month.

Checked#

CheckResult
Controller boardReplaced — only 1 °C better
Temperature readingsMatch
Valve position feedbackLooked normal

Diagnosis#

The PID settings had been changed many times by different people. The controller was overshooting.

Fix#

  1. Open the HT cooler PID window (TEMP CONTROLLER PARAMETER).
  2. Change all four values, then press UPDATE. Changing only some of them did not help.
ParameterBeforeAfter
03_076_P Gain20.0010.00
03_076_I Integration time160.0 s180.0 s
03_076_D Differentiation time1.0 s0.5 s
03_076_DB Dead band0.10 %0.20 %

Do the test at steady engine speed, not during manoeuvring, because the load is not stable then.

HT cooler PID window with the new settings
HT cooler PID window with the new settings

Result#

At sea the temperature now stays within 1 °C of the set point (set 82.0 °C, actual 82.1 °C). Behaviour during manoeuvring was not checked yet.

HT cooling temperature trend after the change: flat at 82 °C for one hour
HT cooling temperature trend after the change: flat at 82 °C for one hour