Main air compressor will not start, contactor does not pull in

Compressed AirElectrical

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Comments · 0

Symptoms#

  • One main air compressor was opened up for overhaul. Then the other one stopped starting, both in auto and in manual.
  • Pressing Start did nothing.

Checked#

CheckResult
FusesOK
Supply to the contactorPresent
Control relay contactsWorking correctly
Control voltage at the main contactor coilPresent
Main contactor, outsideLooked normal

Diagnosis#

The main contactor got control voltage but did not close. When it was taken apart, one leg of the coil terminal A1 was found broken off. The coil read infinite resistance (open circuit). This was the cause; the compressor problem was solved once it was found.