Main air compressor will not start, contactor does not pull in
EL-0091 · Solved · rating 0 · works for 0 engineers · occurred 30 Oct 2019
Source: /cases/el-0091
Symptoms#
- One main air compressor was opened up for overhaul. Then the other one stopped starting, both in auto and in manual.
- Pressing Start did nothing.
Checked#
| Check | Result |
|---|---|
| Fuses | OK |
| Supply to the contactor | Present |
| Control relay contacts | Working correctly |
| Control voltage at the main contactor coil | Present |
| Main contactor, outside | Looked normal |
Diagnosis#
The main contactor got control voltage but did not close. When it was taken apart, one leg of the coil terminal A1 was found broken off. The coil read infinite resistance (open circuit). This was the cause; the compressor problem was solved once it was found.