Ballast valve remote control: half the valves stop responding, no alarm

Ballast SystemAutomation / PLCUtsuki valve remote control, Yokogawa FA-M3 PLC

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • About half of the hydraulic ballast valves stopped responding, all at the same time.
  • No reaction from the ballast console or from the local control panel.
  • No alarms.
  • The valves could still be moved by pressing the manual pin on the solenoid valve with a needle.
  • In the solenoid valve cabinet, three PLC output modules had no lights.
Yokogawa FA-M3 PLC rack in the solenoid valve cabinet
Yokogawa FA-M3 PLC rack in the solenoid valve cabinet
Three YD64-1P DC output modules with no lights
Three YD64-1P DC output modules with no lights

Checked#

CheckResult
Hydraulic power packStarts, hydraulics OK
Power supply to the cabinetsPresent everywhere
System restartDid not help

Diagnosis#

The UPS (uninterruptible power supply) of the system gave only 170 V.

Fix#

  1. Switched off all power to the system, including the computers in the engine control room and the ballast room, for about one hour.
  2. Re-crimped all the contacts.
  3. Replaced the UPS.

Result#

The ballast valves worked again.