Fire pump 115 kW: main breaker trips at star-delta changeover

PumpsElectrical

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Two fire pumps, 115 kW each. One starts normally.
  • The other runs up on star without problems. At the changeover to delta, the main breaker trips.
  • At the changeover, the current goes off the scale of the clamp meter.

Checked#

CheckResult
Contactors, thermal overload relay, main breakerAll replaced with new — no change
Starter with motor cables disconnectedContactors and timer work normally
Star-delta timer delayChanged — no change
Contactor sequenceStar opens first, then delta closes — OK
ConnectionsTight
Insulation phase to phase and to earthOK
Cable continuity, from terminal box and from MSBOK
Pump turned by handTurns freely

Diagnosis#

The delta circuit in the starter was wired wrong. Someone had worked on this wiring before.

For a correct delta (check with power off):

  • On the motor side, the phase order of the main contactor and the delta contactor must match.
  • The delta contactor must join the start of each winding to the end of the next one. For example, with supply A-B-C, the order on the delta contactor is C-A-B.

Fix#

Rewired the delta circuit correctly.

Result#

The fault is gone.