Fire pump 115 kW: main breaker trips at star-delta changeover
EL-0097 · Solved · rating 0 · works for 0 engineers · occurred 28 Feb 2020
Source: /cases/el-0097
Symptoms#
- Two fire pumps, 115 kW each. One starts normally.
- The other runs up on star without problems. At the changeover to delta, the main breaker trips.
- At the changeover, the current goes off the scale of the clamp meter.
Checked#
| Check | Result |
|---|---|
| Contactors, thermal overload relay, main breaker | All replaced with new — no change |
| Starter with motor cables disconnected | Contactors and timer work normally |
| Star-delta timer delay | Changed — no change |
| Contactor sequence | Star opens first, then delta closes — OK |
| Connections | Tight |
| Insulation phase to phase and to earth | OK |
| Cable continuity, from terminal box and from MSB | OK |
| Pump turned by hand | Turns freely |
Diagnosis#
The delta circuit in the starter was wired wrong. Someone had worked on this wiring before.
For a correct delta (check with power off):
- On the motor side, the phase order of the main contactor and the delta contactor must match.
- The delta contactor must join the start of each winding to the end of the next one. For example, with supply A-B-C, the order on the delta contactor is C-A-B.
Fix#
Rewired the delta circuit correctly.
Result#
The fault is gone.