Carel ir33 refrigeration controller: alarm E05 when setpoint is below -18 °C
EL-0102 · Solved · rating 0 · works for 0 engineers · occurred 07 Dec 2019
Source: /cases/el-0102
Contents
Symptoms#
- With the setpoint at -18 °C everything works.
- With the setpoint at -18.5 °C or lower, alarm E05 comes.
- The plant still works and reaches -18.5, -19, -20 °C as set, but the alarm stays.
Diagnosis#
E05 is the low temperature alarm. Its limit is set in parameter P25. With a lower setpoint the temperature goes below this limit.
Fix#
Set the low temperature alarm limit in P25 below the new setpoint.