Carel ir33 refrigeration controller: alarm E05 when setpoint is below -18 °C

Refrigeration & HVACCarel ir33E05

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Comments · 0

Symptoms#

  • With the setpoint at -18 °C everything works.
  • With the setpoint at -18.5 °C or lower, alarm E05 comes.
  • The plant still works and reaches -18.5, -19, -20 °C as set, but the alarm stays.

Diagnosis#

E05 is the low temperature alarm. Its limit is set in parameter P25. With a lower setpoint the temperature goes below this limit.

Fix#

Set the low temperature alarm limit in P25 below the new setpoint.