Scania generator (DEC2): fires 2 or 3 times at start, then fuel is cut off
EL-0103 · Solved · rating 0 · works for 0 engineers · occurred 07 Jan 2020
Source: /cases/el-0103
Symptoms#
- The diesel generator cranks and fires 2–3 times, as if trying to start.
- Then the fuel supply stops and the engine does not start.
- Fuel comes back only after the DEC2 digital engine control system switches off.
- No overspeed alarm.
Checked#
| Check | Result |
|---|---|
| Oil pressure switch | Closed at standstill, opens when the engine starts — OK |
| Low oil pressure / high coolant temperature shutdowns | Disabled with the DIP switch in the DEC2 unit — still no start |
Diagnosis#
The DEC2 digital engine control unit was faulty.
Fix#
Fitted a new DEC2 control unit.
Result#
The generator started at once.
Comments · 0
No comments yet.