Sauer air compressor keeps tripping, nothing found by hand

Compressed AirElectricalSauer

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The air compressor tripped again and again for about 1.5 years.

Checked#

CheckResult
Wiring and connections, by handSeemed OK
Infrared thermometer (spot "gun")Nothing clear
Thermal imagerOne phase about 20–30 °C warmer than the other two
Cable marking on the hot phaseSmaller cross-section than the other phases

Diagnosis#

Inside the box, one phase core had been replaced at some time with a thinner one: cross-section 45 instead of 60. This phase overheated, and the other two phases were also warmer because of the imbalance.

Fix#

Replaced the undersized core with one of the correct cross-section.

Result#

The trips stopped. With the thermal imager the fault was found in about 3 minutes, and the long-standing problem was fixed in about an hour.