Sauer air compressor keeps tripping, nothing found by hand
EL-0111 · Solved · rating 0 · works for 0 engineers · occurred 18 Dec 2023
Source: /cases/el-0111
Symptoms#
- The air compressor tripped again and again for about 1.5 years.
Checked#
| Check | Result |
|---|---|
| Wiring and connections, by hand | Seemed OK |
| Infrared thermometer (spot "gun") | Nothing clear |
| Thermal imager | One phase about 20–30 °C warmer than the other two |
| Cable marking on the hot phase | Smaller cross-section than the other phases |
Diagnosis#
Inside the box, one phase core had been replaced at some time with a thinner one: cross-section 45 instead of 60. This phase overheated, and the other two phases were also warmer because of the imbalance.
Fix#
Replaced the undersized core with one of the correct cross-section.
Result#
The trips stopped. With the thermal imager the fault was found in about 3 minutes, and the long-standing problem was fixed in about an hour.