Alfa Laval boiler: both HMI panels show "Comm err station 0"

BoilerAutomation / PLCAlfa Laval, Beijer HMIController1_TCP: Comm err station 0

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • After the boiler control power was switched off and on, neither HMI panel started working: not the local panel, not the one in the ECR.
  • Both panels showed only the start screen with "Controller1_TCP: Comm err station 0" and "Offline1".
Local HMI panel after the restart: "Controller1_TCP: Comm err station 0", "Offline1"
Local HMI panel after the restart: "Controller1_TCP: Comm err station 0", "Offline1"

Checked#

  • LAN cables in the boiler control cabinet: on one cable the link/activity LED was not lit.
  • That cable was traced to the controller CPU unit.

Diagnosis#

The controller CPU unit was switched off and did not start by itself when power came back. Without it, the HMI panels had nothing to talk to. The unit has a very small, well-hidden power button.

Fix#

Pressed the power button on the CPU unit.

Controller CPU unit in the boiler control cabinet; the arrow shows where the small power button is
Controller CPU unit in the boiler control cabinet; the arrow shows where the small power button is

Result#

The CPU started, both HMI panels came online and everything worked.