Alfa Laval boiler: both HMI panels show "Comm err station 0"
EL-0112 · Solved · rating 0 · works for 0 engineers · occurred 29 Aug 2025
Source: /cases/el-0112
Symptoms#
- After the boiler control power was switched off and on, neither HMI panel started working: not the local panel, not the one in the ECR.
- Both panels showed only the start screen with "Controller1_TCP: Comm err station 0" and "Offline1".
Checked#
- LAN cables in the boiler control cabinet: on one cable the link/activity LED was not lit.
- That cable was traced to the controller CPU unit.
Diagnosis#
The controller CPU unit was switched off and did not start by itself when power came back. Without it, the HMI panels had nothing to talk to. The unit has a very small, well-hidden power button.
Fix#
Pressed the power button on the CPU unit.
Result#
The CPU started, both HMI panels came online and everything worked.