Engine room fan trips its breaker when the soft starter switches to bypass
EL-0023 · Solved · rating 0 · works for 0 engineers · occurred 26 Mar 2025
Source: /cases/el-0023
Symptoms#
- The main engine room supply fan is reversible and is started by a soft starter with a bypass contactor.
- The soft starter ran the fan up normally in about 15 seconds.
- At the moment the bypass contactor closed, the main breaker of the starter tripped. Sometimes the fan started twice and tripped on the third start.
- Running current was 38–40 A. The weather was very hot (near the equator), so the soft starter was suspected first.
Checked#
- Replaced both contactors with new ones. Continuity good, but the fault stayed the same.
- The starter panel room has good ventilation (door open), so heat in the panel was not the cause.
Diagnosis#
The fault was not electrical. On the fan's vent head (mushroom), the damper flap had dropped down from vibration and closed the damper. With the closed damper the motor drew 38–40 A. This is the limit of the 40 A breaker, so the breaker tripped on current as soon as the motor went to direct supply through the bypass.
Fix#
Opened the damper flap on the vent head.
Result#
Running current dropped to 34 A.