Provision plant compressor does not stop at pump-down, overcurrent trip

Refrigeration & HVAC

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The suction line has two low pressure switches: one stops the compressor, the other opens the unloader valve.
  • When all cold room solenoid valves closed and suction pressure fell, the stop switch did not act. Only the unloader switch acted.
  • After about 5 minutes running like this, the compressor overcurrent relay tripped with an alarm.

Checked#

CheckResult
Discharge pressure19–20 bar
Refrigerant in sight glassVisible
Room temperaturesReach set point
Differential of the stop switch changedCompressor stopped and restarted after 1 second, several times; set back

Diagnosis#

The low pressure stop switch was set wrong, so it did not stop the compressor at pump-down.

Fix#

Re-adjusted the range and differential of the low pressure stop switch:

  • Stop: about 0.3 bar
  • Start: about 1.5 bar

Result#

The compressor stops and starts on the switch and works normally.