Hoppe valve remote control shows open and closed at the same time

Automation / PLCHoppe HOMIP

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • On the HOMIP valve remote control, one electro-hydraulic valve showed "open" and "closed" at the same time.
  • Locally the valve worked correctly and moved fully open and closed.

Diagnosis#

The valve position is read by a small board with reed switches on the actuator. Magnets on the pistons switch them.

A little salt water had got into the terminal box. When it dried, salt stayed on the board and shorted it, so both positions were signalled at once.

Fix#

Cleaned the board with electrical contact cleaner and a soft brush.

Result#

The position indication works correctly.