Damcos slop valve shows 67 % when closed

Automation / PLCDamcos

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • Cargo (slop) valve that can be opened by percent.
  • At 100 % open, the monitor and the local indicator agree.
  • With the valve actually closed, the indicator shows 67 %.
  • When opened to 80 %, the valve wanders between 25 % and 75 %.
Damcos local position indicators on the valve control block
Damcos local position indicators on the valve control block

Diagnosis#

Valves that are opened by percent have their own controller. The slop valves have a separate controller with ZERO and SPAN settings (small removable display). The short manual on board did not mention these controllers.

Fix#

Adjusted ZERO and SPAN on the slop valve controller.

Result#

  • The valve now works from 0 to 100 % with correct indication.
  • It still does not hold 50 % — it drifts. Calibration did not cure this.