EL-0018 · Solved · rating 0 · works for 0 engineers · occurred 27 Feb 2024
Source: /cases/el-0018
Symptoms#
- Cargo (slop) valve that can be opened by percent.
- At 100 % open, the monitor and the local indicator agree.
- With the valve actually closed, the indicator shows 67 %.
- When opened to 80 %, the valve wanders between 25 % and 75 %.
Diagnosis#
Valves that are opened by percent have their own controller. The slop valves have a separate controller with ZERO and SPAN settings (small removable display). The short manual on board did not mention these controllers.
Fix#
Adjusted ZERO and SPAN on the slop valve controller.
Result#
- The valve now works from 0 to 100 % with correct indication.
- It still does not hold 50 % — it drifts. Calibration did not cure this.