Control room console: lamp test, duty engineer call and phone horn all dead
EL-0037 · Solved · rating 0 · works for 0 engineers · occurred 17 Sept 2019
Source: /cases/el-0037
Symptoms#
Several functions of the engine control room console stopped at the same time:
- Lamp test did not work.
- Duty engineer call did not work.
- When the engine room telephone rang, the loud horn in the engine room did not sound.
- A lube oil alarm stayed on.
Checked#
- The drawings showed that the only thing common to all these circuits is the 24 V DC supply.
- At every faulty point there was no 24 V.
- All 24 V relays were in good order, but no supply reached the faulty circuits.
- All the dead wires led to one terminal block with fuses.
Diagnosis#
One fuse in that fuse block was blown. It had been tested for continuity many times, but always in its holder, with the probes on the top and bottom of the fuse. In place, the meter showed continuity, so the fuse looked good. Out of the holder it was clearly blown. The search took two full days because of this.
Fix#
- Take each suspect fuse out of its holder and check continuity on the fuse alone.
- Replace the blown fuse.
Comments · 0
No comments yet.