Switchboard earth lamps do not light, only one of three on lamp test
EL-0089 · Solved · rating 0 · works for 0 engineers · occurred 09 Aug 2026
Source: /cases/el-0089
Contents
Symptoms#
- The insulation resistance monitor (IRM) worked normally.
- The earth lamps did not light.
- With the test button pressed, only one of the three lamps lit.
Diagnosis#
The earth lamps and the IRM are fed through one 3-pole fuse holder (F337, 1 A). After about two hours of tracing, the fault was found there. At the shipyard, the wires had been crimped with ring lugs (made for bolt terminals) and pushed into the clamp terminals of the fuse holder. The clamps were holding the plastic sleeve of the lugs, not the metal. So there was no electrical contact, and only one of the three lamps got its phase. The ship had probably worked like this for about 5 years.
Fix#
Re-made the connections so that the terminals clamp the metal of the wire, not the plastic sleeve.