EL-0072 · Solved · rating 0 · works for 0 engineers · occurred 11 Jun 2024
Source: /cases/el-0072
Symptoms#
- The oil mist detector was fully serviced: optics cleaned, filters changed, negative pressure set as per the manual.
- One week later it showed error E 012.
Checked#
| Check | Result |
|---|---|
| Negative pressure | Set again — no change |
| Filters | Changed again — no change |
| Water in the measuring head | None, all dry |
| Fans blowing on the detector | None |
| Temperature changes | None |
Diagnosis#
The manual lists E.012 as a checksum error, with the remedy "repeat parameter adjustment". In the settings, the parameter for oil mist opacity had been lost.
Fix#
Set the parameters again as per the manual.
Result#
The detector works normally.