Newins IC5000 cold room indicator shows LLLL after reset

Refrigeration & HVACNewins IC5000

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • The cold chamber remote temperature indicator read 6 °C different from the real temperature.
  • The settings were reset as the manual says: hold two keys while switching the power on.
  • After the reset, all channels showed LLLL.
  • Setting it up step by step from the manual did not work: the menu kept going back to the start.
IC5000 cold chamber remote indicator showing LLLL after the reset
IC5000 cold chamber remote indicator showing LLLL after the reset

Diagnosis#

The indicator can work with different sensor types. The reset set the sensor input back to the default, 10V. The real sensors are PT (PT100), so the indicator could not read them.

Fix#

  1. In the settings, change the sensor type from 10V to PT.
  2. Set the channels and the reading corrections again.

Result#

The LLLL readings were gone and the problem was solved.