Panasia PAS-200 isolator: input drops to 6.5 V under load

Automation / PLCPanasia PAS-200

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • New PAS-200 signal isolators (1 input, 2 outputs) were fitted in the cargo control room in place of old ones.
  • With nothing connected, the input voltage was 24 V.
  • With a P/I converter connected, the input voltage dropped to 6.5 V.
  • The green OP LED did not light, and there was no signal on the outputs.
  • The old modules, with the same data plate, worked fine.
New PAS-200 (right): PWR and OP LEDs
New PAS-200 (right): PWR and OP LEDs

Diagnosis#

Inside the module, jumper links select sink or source mode: J11 for the input, JP11 for CH1 output, JP21 for CH2 output. On the new modules the jumper was in the wrong position.

PAS-200 manual: sink/source jumper links J11, JP11, JP21
PAS-200 manual: sink/source jumper links J11, JP11, JP21

Fix#

Opened the module and moved the source/sink jumper to the correct position, as shown in the manual.

Result#

The modules work.