Dual-fuel VLCC: why deck LNG tanks have a water spray system
EL-0152 · Knowledge · rating 0 · occurred 20 Jul 2022
Source: /cases/el-0152
Notes#
The water spray system around deck LNG fuel tanks has two jobs: it cools the tank and nearby structure in a fire, and it protects carbon steel deck and structure from brittle fracture if LNG leaks or spills. This note covers the LNG fuel tanks on the open deck of a dual-fuel VLCC. I don't know the tank maker, model or tank type.
Which rules apply. The Gas Carrier Code is sometimes given as the source of the water spray requirement, but I am not certain of that. A ship that burns LNG as fuel but is not a gas carrier comes under the IGF Code:
- IGF Code 11.5.1: a water spray system is required for cooling and fire prevention.
- IGF Code 11.5.2: the spray must also cover nearby superstructures and other occupied deckhouse boundaries on open deck that face the tank. This extra coverage is not needed if the tank is
10 mor more from those boundaries.
Why the steel matters.
- LNG is stored at about
-162 °C. A spill onto steel plate can crack it, so the deck needs a barrier. - Steel gets less ductile as it gets colder. Normal mild steel turns brittle at around
-10 °C. Carbon steel that LNG touches can crack when it is under load, which puts the hull and deck structure at risk. - Brittle fracture is a carbon steel deck plate problem. It does not apply to stainless steel. Austenitic stainless steel stays ductile at cryogenic temperatures, which is why it is used for drip trays and cryogenic piping.
In short, the water spray around LNG fuel tanks:
- In a fire, cools the tank and the structure near it.
- If LNG leaks or spills, protects carbon steel deck and structures from cold-induced brittle fracture.
What this note doesn't cover: spray capacity or water rate (L/min/m²), nozzle layout, test and maintenance intervals, activation method (manual or automatic), drip tray details, or any maker or class service letter. It is not based on a real incident.