Inert gas oxygen analyzers keep failing: a care routine that works

Fire & Safety

Contents
  1. Scope
  2. Safety
  3. Tools & parts
  4. Steps
  5. Check after
  6. Comments · 0

Scope#

Inert gas (IG) oxygen analyzers that fail again and again are, in my view, usually handled badly or not maintained correctly; this is the care routine I use to prevent it. Repeated failures with expensive repairs are a known problem. I have no ship type, analyzer maker or model, symptoms, readings or alarms for a specific case, and the cause of failure has not been confirmed in any case I know.

Servomex has a good name for IG oxygen analyzers. One shipping company with the same repeated failures switched to Servomex analyzers at the request of ship buyers, and after the change almost no more failures were reported. I am not sure if Servomex still sells these units.

This is my own practice, not a procedure from the analyzer maker.

Safety#

  • Follow the maker's manual and your company procedures for the IG system and the analyzer.
  • Nitrogen is used for purging. Take care with nitrogen and inert gas in closed spaces.
  • Do not let the sample flow rise suddenly. In my experience this may damage the sensor.

Tools & parts#

  • New or cleaned filters for the sample line
  • Clean fresh water for the water filter
  • Fresh air for the span calibration
  • Nitrogen supply for purging

Steps#

Before the inerting job:

  1. I do the filter work 2-3 days ahead: I clean the filters, or fit new ones.
  2. At the same time, I put clean fresh water back in.
  3. I calibrate the sensor 1 day before the job.
  4. The zero calibration normally needs about 2.5-4 min.
  5. The span calibration, done with fresh air, needs about 1.5-2 min.
  6. I keep a flow range of about 50-80 ml/min with the calibration step. Raise the flow slowly, never in one jump.

When inerting is finished and the analyzer will stand idle:

  1. I flush the system with nitrogen. About 2-3 min is enough.
  2. I shut every sampling valve. The nitrogen then stays in the system while it stands idle.
  3. I empty the water filter.
  4. I turn the analyzer's power off.

Check after#

  • Before the next job, check that the sample flow is steady and inside the 50-80 ml/min range.
  • I have no case where the internal fault was identified or where this routine was confirmed to stop repeated failures.