Fire detection: "Cable break positive" fault, but voltage everywhere
EL-0010 · Solved · rating 0 · works for 0 engineers · occurred 10 Aug 2022
Source: /cases/el-0010
Symptoms#
- Fire alarm panel fault: "LOOP ANALOGUE 2 CABLE BREAK POSITIVE, FAULT(141)", engine room area.
- The panel showed the break between SCI (short circuit isolator) address 28 and SCI address 39. There are 11 more devices (detectors and call points) between them.
- 33 V DC measured at every point. All detectors worked. No other faults.
Diagnosis#
The positive wire had pulled out of its terminal at isolator 28.
The loop is fed from both ends. With one break, all detectors still get voltage and work, so voltage checks do not show where the break is.
Fix#
- At isolator 39 (one end of the faulty section), disconnect the loop wire.
- Watch the panel. Devices between the break and 39 lose communication. Here all devices up to 28 dropped out, so the break was at 28.
- At isolator 28 the wire was found pulled out of the terminal. Reconnected it and restored the wire at 39.
Result#
The fault alarm cleared.