Autronica: loop fault on Ex detector stays after barrier replacement
EL-0086 · Solved · rating 0 · works for 0 engineers · occurred 29 Sept 2025
Source: /cases/el-0086
Symptoms#
- Open-circuit fault on the paint store detector line.
- The panel showed "LOOP FAULTS 1 LOOP 01" and "POINT FAULTS 1 10106 SD(EXI)".
- The system did not see the detector.
Checked#
| Check | Result |
|---|---|
| BZB 500 interface unit (Ex barrier) | Swapped with the unit from the battery room line, later replaced with a new one. Fault stayed. |
| Whole line, continuity test | Nothing found |
| Detector base | Replaced with a new one. Fault stayed. |
| Wires to the detector base, visual | Looked normal, no oxide |
Diagnosis#
Bad contact on the wires going to the detector base. The wires looked clean and passed the continuity test, but the panel could not see the detector through them.
Fix#
Cleaned the wires at the detector base with contact cleaner.
Result#
The fault cleared.