Autronica: loop fault on Ex detector stays after barrier replacement

Fire & SafetyAutronica, BZB 500 interface unitLOOP FAULTS: LOOP 01 / POINT FAULTS: 10106 SD(EXI)

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Open-circuit fault on the paint store detector line.
  • The panel showed "LOOP FAULTS 1 LOOP 01" and "POINT FAULTS 1 10106 SD(EXI)".
  • The system did not see the detector.
Fault warnings on the fire alarm panel
Fault warnings on the fire alarm panel

Checked#

CheckResult
BZB 500 interface unit (Ex barrier)Swapped with the unit from the battery room line, later replaced with a new one. Fault stayed.
Whole line, continuity testNothing found
Detector baseReplaced with a new one. Fault stayed.
Wires to the detector base, visualLooked normal, no oxide
BZB 500 interface unit (Ex barrier) in its junction box
BZB 500 interface unit (Ex barrier) in its junction box

Diagnosis#

Bad contact on the wires going to the detector base. The wires looked clean and passed the continuity test, but the panel could not see the detector through them.

Fix#

Cleaned the wires at the detector base with contact cleaner.

Result#

The fault cleared.