Consilium fire detection: five "Sensor fail" alarms from one zone
EL-0106 · Solved · rating 0 · works for 0 engineers · occurred 06 Apr 2020
Source: /cases/el-0106
Symptoms#
- Five "Sensor fail" alarms with "Communication error" came up suddenly, all from one zone (pump room).
- The failed points were on two loops: 3 smoke detectors on loop 2 and 2 manual call points on loop 3.
- The system has only 3 loops and many zones. There is no separate card for each zone, so detectors from different areas share the same loops.
Checked#
| Check | Result |
|---|---|
| Board in the IS (intrinsically safe) box for this zone, input | 24 V present |
| Same board, output | No 24 V |
Diagnosis#
The zener barrier in the IS box had burnt out. All detectors and call points behind it lost supply, so they all failed at once.
Fix#
Replaced the zener barrier board in the IS box.
Result#
All points came back and the system works.