OceanGuard BWTS: "EUT Power Abnormal" 10 s after start

Ballast SystemOceanGuardEUT Power Abnormal Alarm

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The BWTS worked normally 3 days before.
  • Now, about 10 seconds after start, the alarm "EUT Power Abnormal Alarm" came up and the system stopped.
  • The EUT power unit got its supply: LEDs on all modules and its display came on. But EUT voltage and current stayed at 0.
  • The local display of the EUT power unit showed "water pressure alarm 1".
  • On one start the voltage rose to 9 V and the current to 108 A, then the unit shut down at once.
Alarm list: EUT Power Abnormal Alarm after each start attempt
Alarm list: EUT Power Abnormal Alarm after each start attempt

Checked#

CheckResult
Remote and local control panels switched off and onNo change
440 V and 110 V supply to the system switched off at the MSB, then onNo change
EUT power unit temperature (shutdown above 45 °C)19 °C — OK
Cooling water pressure switch (opened and tested)Operates

Diagnosis#

The manual lists two shutdowns for the EUT power unit: temperature above 45 °C and the cooling water pressure switch. Here it was the pressure switch.

  • The fresh water tank for EUT cooling was empty, because of a leak on the cooler.
  • Even with water, the cooling pump gave only 0.5 kg/cm². The manual says 2–3 kg/cm².

Fix#

  1. Filled the cooling fresh water tank.
  2. Adjusted the pressure with the manual valve on the EUT power cooling water outlet to 2.5 kg/cm².
  3. Started the system.

Result#

The system started and ran normally.