BWTS valve with Siemens SIPART PS2 positioner: alarm A29, valve limit switch
EL-0038 · Solved · rating 0 · works for 0 engineers · occurred 06 Aug 2020
Source: /cases/el-0038
Contents
Symptoms#
- The ballast water treatment system gave alarm A29: limit switch fault on a valve.
- The limit switch is inside the valve positioner, wired to terminals 41–42.
Diagnosis#
Vibration had loosened a bolt from the board inside the positioner. The bolt fell between one of the setting wheels and the limit switch, so the switch did not work as it should.
Fix#
Removed the loose bolt from the limit switch module.
Comments · 0
No comments yet.