Kangrim boiler: "Flame failure" alarm while stopped, will not reset
EL-0021 · Solved · rating 0 · works for 0 engineers · occurred 17 Jul 2024
Source: /cases/el-0021
Symptoms#
- FLAME FAILURE alarm came up while the boiler was stopped (not firing).
- The alarm could not be reset. A restart did not help.
Checked#
| Check | Result |
|---|---|
| Timer relay replaced | Alarm stays |
| Relays swapped between places | Alarm stays |
| Contact of flame failure relay 20K6 to PLC input 10 (tester) | Closed |
| 20K6 removed, jumper on PLC input 10 | No input indication on the PLC |
Diagnosis#
The PLC input module that reads the flame failure signal was faulty.
Fix#
Swapped the faulty input module with the next module in the rack (one that uses only a few channels).
Result#
The alarm cleared and the boiler works.