Weishaupt Monarch burner: random "Air combustion low" at start

BoilerWeishaupt MonarchAir combustion low

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The burner tripped only at boiler start, two or three times a day.
  • The alarm changed: sometimes "Air combustion low", sometimes "Flame failure".
  • It was random: no alarm for 10 hours, then up to five alarms.

Checked#

CheckResult
Furnace and tubesOK
Ignition electrodes, atomizers, filtersReplaced — no change
Burner control unit (Siemens LOK16.250A27) swapped with a spare"Air combustion low" twice, then no start after reset. Old unit refitted
Air damper servomotor (opened)Looks normal inside, metal gear

Diagnosis#

The combustion air pressure switch was faulty.

Fix#

Replaced the air pressure switch with a new one from spares.

Result#

The burner starts and works without alarms.