Kangrim boiler: "Flame failure" at the end of the ignition time
EL-0100 · Solved · rating 0 · works for 0 engineers · occurred 05 Oct 2021
Source: /cases/el-0100
Symptoms#
- Composite boiler. It had run in manual for more than a week. When it was switched to auto, the "Flame failure" alarm came.
- The burner starts and the flame burns. The alarm comes at the moment the timer relay ends the ignition time.
- After some parts were changed, the same fault came in manual too.
- The lamp on the Siemens LAE10 flame relay was very dim. Before, it was bright at start.
Checked#
| Check | Result |
|---|---|
| Fuel nozzle | Removed and cleaned, no change |
| Torch light held on the flame sensor | Alarm still comes |
| Fuel pressure | 23 bar (diesel oil) |
| Ignition electrode | Replaced, no change |
| Flame sensor glass | Replaced, no change |
| Timer relay | Replaced, no change |
| LAE10 flame relay | Replaced, lamp still dim |
| Supply voltage | 220 V present |
| Flame sensor cables | Continuity OK |
| Flame sensors (one for manual, one for auto) | Same fault with both |
Diagnosis#
The burner servo motor did not go back to 0° in its start position. It stood at 5°. Its setting had drifted.
Fix#
Adjusted the servo motor so that its start position is 0°.
Result#
The boiler starts and runs normally.