Kangrim boiler: "Flame failure" at the end of the ignition time

BoilerKangrimFlame failure

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Composite boiler. It had run in manual for more than a week. When it was switched to auto, the "Flame failure" alarm came.
  • The burner starts and the flame burns. The alarm comes at the moment the timer relay ends the ignition time.
  • After some parts were changed, the same fault came in manual too.
  • The lamp on the Siemens LAE10 flame relay was very dim. Before, it was bright at start.

Checked#

CheckResult
Fuel nozzleRemoved and cleaned, no change
Torch light held on the flame sensorAlarm still comes
Fuel pressure23 bar (diesel oil)
Ignition electrodeReplaced, no change
Flame sensor glassReplaced, no change
Timer relayReplaced, no change
LAE10 flame relayReplaced, lamp still dim
Supply voltage220 V present
Flame sensor cablesContinuity OK
Flame sensors (one for manual, one for auto)Same fault with both

Diagnosis#

The burner servo motor did not go back to 0° in its start position. It stood at 5°. Its setting had drifted.

Fix#

Adjusted the servo motor so that its start position is 0°.

Result#

The boiler starts and runs normally.