AMS Totem Plus: ME Alpha Lubricator alarms go into inhibit

Automation / PLCMain EngineTotem Plus IMACS

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Comments · 0

Symptoms#

  • At sea, all ME Alpha Lubricator alarms on the AMS (about 6 channels) went into inhibit by themselves.
  • Real alarms on the Alpha Lubricator panel did not come to the AMS. Alpha Lubricator solenoid valves failed from time to time, and no alarm was given.
  • Of the machinery, only two diesel generators and the emergency generator were in inhibit at that time.
  • On this AMS version a channel's settings cannot be opened by double-click. Only delay and off-scan (alarm off) can be set, through Alarm Tolerance.

Diagnosis#

The Alpha Lubricator alarms had been put in the inhibit group of DG1. When DG1 was stopped, its alarm blocking was active, so all Alpha Lubricator alarms were inhibited too.

On IMACS, General > Inhibits lists the inhibit sources (for example "NO.1 G/E ALARM BLOCKING"). Double-click one to see all signals it blocks.

Inhibits list (General > Inhibits), newer IMACS version
Inhibits list (General > Inhibits), newer IMACS version
Double-click an inhibit to see which signals it blocks
Double-click an inhibit to see which signals it blocks

Fix#

  1. Temporary: keep DG1 running. Its inhibit is then off, and the Alpha Lubricator alarms come to the AMS.
  2. Permanent: move the Alpha Lubricator channels out of the DG1 inhibit group in the AMS configuration. This could not be done on board; it needs instructions and a password from the AMS maker.