DEIF PPM-3: busbar voltage read too low, generator will not auto-synchronise

Automation / PLCElectricalDEIF PPM-3

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The DEIF PPM-3 controller of one generator measured the busbar voltage lower than it really was.
  • The PMS saw a voltage fault. Auto synchronising was not possible, only manual.
  • When the measured busbar voltage dropped to 350 V, the generator could not be connected to the busbar in manual or in auto.

Checked#

CheckResult
Voltage from the generatorsNormal
Voltage at the PPM-3 voltage input terminalsNormal

So the correct voltage reached the PPM-3, but the controller read it too low.

Diagnosis#

The Voltage Measuring Card inside the PPM-3 had failed. This card is a known weak point of the PPM-3.

Fix#

Temporary, to make auto-sync possible:

ParameterFactory valueChanged to
1300 SP set-point90 %84 %
2020 dUmax5 %14 %
2110 dUmax5 %14 %

With these settings everything works in auto. The office was informed. Put the factory values back before the card is replaced. The DEIF Designer's Reference Handbook and the parameter list for the PPM-3 explain these settings.

Permanent:

  1. Take a backup of the PPM-3 program with the DEIF USW3 utility software (USB cable, printer type).
  2. Replace the Voltage Measuring Card (ordered through DEIF).
  3. Load the backup back into the PPM-3.

Result#

Problem solved.