▲0 rating0 commentsEmergency generator: all alarms when the rack bracket is releasedKnowledgeAuxiliary EngineAfter a manual (emergency) start, the fuel rack is held by a locking bracket. If this bracket is released while the engine runs, the engine stops at once and all alarms come up together.Anonymous · 7 y▲0 rating0 commentsHyundai generator: no voltage at start after a 440 V insulation alarmTroubleshootingElectrical · Hyundai HFC7The 440 V insulation reading started to jump between 0 and infinity. Three generators were on the bus. Two were taken off, only No. 3 was left. Next day generator No. 1 was started, but it did not…Anonymous · 4 y▲0 rating0 commentsGenerator will not come off the bus at stop: "Stop failure", reverse powerTroubleshootingElectrical · Stop failureThe undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt. To keep the breaker usable, the UV coil plunger was held in with its mechanical lock. The generator synchronised and…Anonymous · 1 y▲0 rating0 commentsDaihatsu 6DK generator: testing overspeed without a test buttonKnowledgeAuxiliary Engine · Anqing Daihatsu 6DK, Nanjing Chuzheng speed switchThe generator engine has a separate speed switch unit (Nanjing Chuzheng). It has no test button. The settings on its label: Setting Value Low speed 300 rpm Rated speed 720 rpm Overspeed 815 rpm…Anonymous · 6 y▲1 rating0 commentsHyundai HV switchboard: generator VCB tripped, no reset buttonTroubleshootingElectrical · Hyundai HIMAP-BCThe generator engine shut down on lube oil. HIMAP showed reverse power, and the generator VCB (6600 V) tripped. The breaker could not be reset at the breaker. There is no reset button and no handle…Anonymous · 7 mo▲0 rating0 commentsEmergency generator runs but its breaker will not close on blackoutTroubleshootingElectricalEmergency generator load test: the MSB–ESB transfer breaker was opened. The emergency generator started normally. Its breaker did not close onto the ESB bus.Anonymous · 3 y▲0 rating0 commentsEmergency generator breaker closes and opens again at once, no tripTroubleshootingElectrical · Schneider Masterpact NT06 H2, Micrologic 5.0 AThe emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode. On "close" the breaker clicked and closed. The green "closed" indication was on…Anonymous · 4 y▲0 rating0 commentsEmergency generator: insulation drops to 0.1 MΩ at every startTroubleshootingElectrical · Low insulation 440 VEvery time the emergency generator started, the 440 V insulation monitor fell to 0.1–0.2 MΩ. After 2–3 hours of running, the reading slowly came back to normal (5 MΩ and higher). The ship had been…Anonymous · 7 y▲0 rating0 commentsDoosan emergency generator: testing overspeed without a test buttonKnowledgeAuxiliary Engine · Doosan AD136TS, KMC ECMS-850EH · OverspeedThe set: Doosan AD136TS engine (1800 rpm, 125 kW) with a KMC ECMS-850EH engine control and monitoring system. The wiring diagram in the manual shows a GAC ESD5550 speed control unit with "TEST…Anonymous · 3 y▲0 rating0 commentsScania generator (DEC2): fires 2 or 3 times at start, then fuel is cut offTroubleshootingAuxiliary Engine · Scania, DEC2 digital engine controlThe diesel generator cranks and fires 2–3 times, as if trying to start. Then the fuel supply stops and the engine does not start. Fuel comes back only after the DEC2 digital engine control system…Anonymous · 6 y▲0 rating0 commentsYanmar generator: HT cooling water outlet 6 °C hotter than on the other engineTroubleshootingAuxiliary Engine · Yanmar (450 kW)Two Yanmar 450 kW generators in parallel, about 300 kW each. Engine HT inlet HT outlet Engine 1 76 °C 80 °C Engine 2 76 °C 86 °CAnonymous · 2 y▲0 rating0 commentsDEIF PPM-3: busbar voltage read too low, generator will not auto-synchroniseTroubleshootingAutomation / PLC · DEIF PPM-3The DEIF PPM-3 controller of one generator measured the busbar voltage lower than it really was. The PMS saw a voltage fault. Auto synchronising was not possible, only manual. When the measured…Anonymous · 2 y▲0 rating0 commentsEmergency generator will not crank on batteries that test OKTroubleshootingAuxiliary EngineThe emergency generator did not start on the electric starter, from the remote panel or from the local panel on the engine. The engine turned over once or twice, then stopped cranking. The start…Anonymous · 4 y▲0 rating0 commentsCaterpillar 3408 generator will not start after blackoutTroubleshootingAuxiliary Engine · Caterpillar 3408The generator engine stopped and caused a blackout. Dirty fuel filters had let air into the fuel system. After the filters were changed, the engine cranked on the air starter but did not start.Anonymous · 3 y▲0 rating0 commentsYanmar generators: look-alike turbochargers are not interchangeableKnowledgeTurbocharger · YanmarA ship had three Yanmar diesel generators: two with 1600 kW generators and one with a 1200 kW generator. The diesel engines were the same, and the turbochargers looked the same from outside. But the…Anonymous · 2 y▲0 rating0 commentsEmergency generator trips on blackout test, then will not close on the busTroubleshootingElectrical · Schneider Electric ComPacT NSX630Blackout test from the main switchboard: the supply to the emergency switchboard was switched off. The emergency generator started, closed onto the bus and took the load. After 5–10 minutes it…Anonymous · 6 mo▲0 rating0 commentsTerasaki PMS: generator will not parallel in auto, "ACB non close"TroubleshootingElectrical · Terasaki PMS · ACB non closeWhen a generator was put in parallel in automatic mode, the alarm "ACB non close" came up. The breaker did not close and the engine stayed running with no load. Frequency and voltage were the same as…Anonymous · 4 y▲0 rating0 commentsCummins NTA855 emergency generator: speed hunts ±30 rpm after a cold startTroubleshootingAuxiliary Engine · Cummins NTA855-D(M)On the first cold start, speed hunted by about ±30 rpm at 1800 rpm (frequency by about 0.5 Hz). After a restart (sometimes the 2nd or 3rd) it ran smoothly, and further starts were fine. A few hours…Anonymous · 1 y▲0 rating0 commentsYanmar generator: low LO pressure shutdown 5 minutes after startTroubleshootingAuxiliary Engine · YanmarAfter start, LO pressure was normal (4.8 bar), then slowly fell. After 5–6 minutes at most, the engine shut down on low LO pressure. The differential pressure indicator on the automatic LO filter…Anonymous · 4 y▲0 rating0 commentsGenerator engine fails on non-OEM bearings run to OEM intervals (Kommandor Susan)IncidentAuxiliary Engine · Caterpillar 3516B-TA · ER fire alarm, blackoutDiesel-electric vessel on sea trials, just out of the lock at Leith with a pilot on board. DG1 and DG4 were on line. The C/E heard a change in engine note on one generator, then a loud bang. The fire…Anonymous · 6 mo▲0 rating0 commentsGenerator overhaul: checklist to prevent con-rod failures afterwardsProcedureAuxiliary EngineMost serious damage to an auxiliary diesel generator (D/G) comes a few hours after a general overhaul, usually from connecting rod or rod bolt failure; this is the checklist I use to prevent it. It…Anonymous · 4 y▲0 rating0 commentsUsing a new bunker before the lab report arrives: precautionsProcedureMain EngineWhen a ship has to change over to a new bunker before the lab report arrives, I treat the fuel as suspect and run with extra precautions on fuel treatment and engines until the result is known. The…Anonymous · 4 y▲0 rating0 commentsFresh water generator: checklist for low output or high salinityProcedureFresh Water GeneratorThis is my checklist for a fresh water generator (FWG) that makes too little water or gives high salinity in the distillate. It applies to a vacuum evaporator heated by engine jacket water, where an…Anonymous · 4 y▲0 rating0 commentsGenerator con-rod seizes and holes the block: oil run far past interval (Ocean Navigator)IncidentAuxiliary Engine · Caterpillar 3516B · ER fire alarm, AE2 low LO pressure and oil filter plugged, blackoutAE2 on a coastal cruise ship (Caterpillar 3516B, 1,800 rpm) had run its LO for more than 5,000 h and its filter elements for 3,329 h. Both should be changed at 1,000 h (LO longer only under…Anonymous · 1 y▲0 rating0 commentsMain switchboard low insulation: find the fault by isolating loadsProcedureElectrical · Low insulationThis is how I find the cause of a low insulation alarm or low reading on the main switchboard (MSB): isolate all loads, then reconnect them one at a time while watching the insulation monitor. It…Anonymous · 4 y▲0 rating0 commentsAMS Totem Plus: ME Alpha Lubricator alarms go into inhibitTroubleshootingAutomation / PLC · Totem Plus IMACSAt sea, all ME Alpha Lubricator alarms on the AMS (about 6 channels) went into inhibit by themselves. Real alarms on the Alpha Lubricator panel did not come to the AMS. Alpha Lubricator solenoid…Anonymous · 8 mo▲0 rating0 commentsEngine room flooding from a corroded sea water pipe at the strainer (Oliver Hazard Perry)IncidentAuxiliary Engine · John Deere diesel generator · AC power fault alarm on fire alarm panel, blackoutSail training tall ship (128 ft), two Caterpillar C12 propulsion engines, two John Deere DGs (99 kW). Moored, one crewmember on board. Shore power breakers kept tripping, so the port DG ran…Anonymous · 7 mo▲0 rating0 commentsAlfa Laval plate FWG: high brine temperature (60 °C) and low outputTroubleshootingFresh Water Generator · Alfa Laval (plate type)Low fresh water output and brine temperature up to 60 °C. Cleaning the plates did not help. Vacuum and heating water were normal. Readings, the same before and after cleaning: Reading Value Heating…Anonymous · 10 mo▲0 rating0 commentsAux engine room fire: slipped fuel pump coupling and exhaust leak (Finnmaster)IncidentAuxiliary Engine · Mitsubishi S12R · ER smoke alarm, then blackoutRo-ro leaving Hull with a pilot on board. AE1 had just been paralleled with AE2. Eight minutes after leaving the berth, smoke was detected in the aux engine room. Both AE2 exhaust temperature gauges…Anonymous · 1 y▲0 rating0 commentsStandard bearing shell on an undersize journal: con-rods break out (Ocean Guardian)IncidentAuxiliary Engine · Caterpillar 3516B · No alarm; loud bang, then smoke and fire in ERDiesel-electric offshore supply vessel, four Caterpillar 3516B main DGs (1,990 kW each). All four were overhauled by shore technicians in early 2022. On sea trials, DG3 had run about 4 h since…Anonymous · 3 y