Hi Air Korea AC: compressor will not start, "FRESH ARM 1CRUN"

Refrigeration & HVACHi Air KoreaFRESH ARM 1CRUN

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • The AC compressor did not start. No alarms were showing.
  • When starting the compressor, only the controller on the AC control panel showed a new alarm: FRESH ARM 1CRUN.
  • The manuals do not explain this alarm.
AC panel controller alarm list showing FRESH ARM 1CRUN
AC panel controller alarm list showing FRESH ARM 1CRUN

Diagnosis#

The compressor start depends on the fresh-air temperature sensor. The settings plate on the panel lists "Temp. sensor for fresh air (QAM2120)": cooling start 23.0 °C, cooling stop 20.0 °C. The outside air was below 20 °C, so the controller blocked the compressor start and showed the "FRESH" alarm.

Fix#

Moved the fresh-air temperature sensor out of the outside-air suction duct to inside the room.

Fresh-air temperature sensor taken out of the outside-air suction duct
Fresh-air temperature sensor taken out of the outside-air suction duct

Result#

The alarm cleared.