Bock compressor (AC plant): oil solenoid valve coils overheat and melt

Refrigeration & HVACBock

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Notes
  5. Comments · 0

Symptoms#

  • AC plant with a Bock compressor. The coil of the oil solenoid valve (220 V, 60 Hz, 10 W) burnt.
  • A new coil heated up very fast and melted. The next coils melted too.
  • Before this, everything had worked normally.

Diagnosis#

The valve stem (plunger) was stuck in the top position, or above it.

The oil solenoid valve removed from the compressor; the coil sits on the stem tube
The oil solenoid valve removed from the compressor; the coil sits on the stem tube

Fix#

Replaced the valve. Until it was replaced, every new coil melted.

Notes#

  • The coils are marked with a maximum temperature of +40…80 °C. If a coil gets to about 100 °C, the plunger is stuck somewhere.
  • A new coil alone does not help while the plunger is stuck.