Bock compressor (AC plant): oil solenoid valve coils overheat and melt
EL-0076 · Solved · rating 0 · works for 0 engineers · occurred 04 Jan 2025
Source: /cases/el-0076
Symptoms#
- AC plant with a Bock compressor. The coil of the oil solenoid valve (220 V, 60 Hz, 10 W) burnt.
- A new coil heated up very fast and melted. The next coils melted too.
- Before this, everything had worked normally.
Diagnosis#
The valve stem (plunger) was stuck in the top position, or above it.
Fix#
Replaced the valve. Until it was replaced, every new coil melted.
Notes#
- The coils are marked with a maximum temperature of +40…80 °C. If a coil gets to about 100 °C, the plunger is stuck somewhere.
- A new coil alone does not help while the plunger is stuck.