AC plant with two compressors: valves do not open on one compressor
EL-0110 · Solved · rating 0 · works for 0 engineers · occurred 12 Sept 2022
Source: /cases/el-0110
Symptoms#
- AC plant with two compressors on one large AHU.
- With one compressor running alone, the refrigerant valves to the AHU cooling coil did not open. The controller gave no open command at all.
- The problem had been there for a long time. Long ago the plant ran on one compressor.
Checked#
| Check | Result |
|---|---|
| Other parameters against the manual | Changed, no real effect |
| Configuration → System → Compression regulation system: change from "Sequence" | Alarm at once |
Fix#
On the controller touch screen:
- Configuration → System → Compression regulation system: set "Cascade".
- Configuration → Plant → Compressor operation mode: change "Compr1 manual - Compr2" to "Disabled".
Result#
The plant works with one compressor and with both together, and the regulation works.