AC plant with two compressors: valves do not open on one compressor

Refrigeration & HVAC

Contents
  1. Symptoms
  2. Checked
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • AC plant with two compressors on one large AHU.
  • With one compressor running alone, the refrigerant valves to the AHU cooling coil did not open. The controller gave no open command at all.
  • The problem had been there for a long time. Long ago the plant ran on one compressor.

Checked#

CheckResult
Other parameters against the manualChanged, no real effect
Configuration → System → Compression regulation system: change from "Sequence"Alarm at once

Fix#

On the controller touch screen:

  1. Configuration → System → Compression regulation system: set "Cascade".
  2. Configuration → Plant → Compressor operation mode: change "Compr1 manual - Compr2" to "Disabled".
Compression regulation system: Separated / Sequence / Cascade
Compression regulation system: Separated / Sequence / Cascade
Compressor operation mode: was "Compr1 manual - Compr2", set to "Disabled"
Compressor operation mode: was "Compr1 manual - Compr2", set to "Disabled"

Result#

The plant works with one compressor and with both together, and the regulation works.