Main switchboard low insulation: find the fault by isolating loads
EL-0183 · Procedure · rating 0 · occurred 25 Aug 2022
Source: /cases/el-0183
Scope#
This is how I find the cause of a low insulation alarm or low reading on the main switchboard (MSB): isolate all loads, then reconnect them one at a time while watching the insulation monitor. It covers the 440V and 220V buses and uses the insulation (earth fault) monitor on the switchboard. It is not tied to a particular maker or model.
Safety#
- Opening consumer breakers stops that equipment. If you open all of them, essential services can lose power. Plan this with the bridge and the engine team before you start.
- I don't have a set method for essential consumers that cannot be stopped. Agree a safe plan for them on board before you open their breakers.
- Do not bypass any safety device or interlock during the test.
Tools & parts#
- Insulation (earth fault) monitor on the MSB.
- I don't use any other meter or tool in this method.
Steps#
- Deal with a low insulation alarm without delay. Problems left to build up are much harder to fix.
- Disconnect all loads from the bus.
- Check the insulation monitor. With no load connected, it should show infinity.
- Reconnect the loads one by one. Check the monitor after each one.
- If the reading falls when a load is connected, treat that load as faulty and inspect it.
- On the
440Vside, I suspect the generator first. Close the generator ACB to the bus and watch the monitor. - If the reading falls when the generator ACB closes, the fault is on the generator side.
- If the reading recovers when the ACB is opened again, inspect the circuit between the ACB and the alternator.
Check after#
- After the faulty circuit is found and repaired, check the monitor reading again with the loads connected.
- What this note doesn't cover: acceptable insulation values in megohms, meter type, whether to megger the isolated circuits, special points for the
220Vside, or the outcome of a real case.