Daihatsu 6DK generator: testing overspeed without a test button
EL-0105 · Knowledge · rating 0 · occurred 13 Mar 2020
Source: /cases/el-0105
Notes#
The generator engine has a separate speed switch unit (Nanjing Chuzheng). It has no test button. The settings on its label:
| Setting | Value |
|---|---|
| Low speed | 300 rpm |
| Rated speed | 720 rpm |
| Overspeed | 815 rpm |
| Reduction gear ratio | 2 |
The unit has three relay outputs: OVER on terminals 10–11–12, RATED on 13–14–15, LOW on 16–17–18.
How the shutdown was tested#
- Run the generator.
- Put a jumper between terminals 10 and 12 (OVER contact).
- The overspeed protection operated and the engine stopped.
Comments · 0
No comments yet.