Daihatsu 6DK generator: testing overspeed without a test button

Auxiliary EngineAnqing Daihatsu 6DK, Nanjing Chuzheng speed switch

Notes#

The generator engine has a separate speed switch unit (Nanjing Chuzheng). It has no test button. The settings on its label:

SettingValue
Low speed300 rpm
Rated speed720 rpm
Overspeed815 rpm
Reduction gear ratio2

The unit has three relay outputs: OVER on terminals 10–11–12, RATED on 13–14–15, LOW on 16–17–18.

Speed switch label with the speed settings and the OVER / RATED / LOW contact terminals
Speed switch label with the speed settings and the OVER / RATED / LOW contact terminals

How the shutdown was tested#

  1. Run the generator.
  2. Put a jumper between terminals 10 and 12 (OVER contact).
  3. The overspeed protection operated and the engine stopped.

Comments · 0

No comments yet.

Sign in to comment, vote and confirm fixes.Sign in