Doosan emergency generator: testing overspeed without a test button

Auxiliary EngineDoosan AD136TS, KMC ECMS-850EHOverspeed

Notes#

The set: Doosan AD136TS engine (1800 rpm, 125 kW) with a KMC ECMS-850EH engine control and monitoring system.

The wiring diagram in the manual shows a GAC ESD5550 speed control unit with "TEST OVERSPEED" and "RESET OVERSPEED" buttons. That drawing is for another engine model (AD086TI). This set has no such unit, and there is no overspeed test button inside the panel.

Manual drawing for another model: GAC ESD5550 with TEST / RESET OVERSPEED buttons, not fitted on this set
Manual drawing for another model: GAC ESD5550 with TEST / RESET OVERSPEED buttons, not fitted on this set

The overspeed setting is on the "Alarm & Trip Table" plate on the control panel: 2016–2070 rpm.

Control panel with KMC ECMS-850EH; the Alarm & Trip Table gives overspeed at 2016–2070 rpm
Control panel with KMC ECMS-850EH; the Alarm & Trip Table gives overspeed at 2016–2070 rpm

How the alarm was tested#

  1. Start the emergency generator.
  2. Move the fuel injection pump rack by hand to raise the speed.
  3. The Overspeed alarm comes up on the ECMS-850EH.