Doosan emergency generator: testing overspeed without a test button
EL-0012 · Knowledge · rating 0 · occurred 16 Jan 2023
Source: /cases/el-0012
Notes#
The set: Doosan AD136TS engine (1800 rpm, 125 kW) with a KMC ECMS-850EH engine control and monitoring system.
The wiring diagram in the manual shows a GAC ESD5550 speed control unit with "TEST OVERSPEED" and "RESET OVERSPEED" buttons. That drawing is for another engine model (AD086TI). This set has no such unit, and there is no overspeed test button inside the panel.
The overspeed setting is on the "Alarm & Trip Table" plate on the control panel: 2016–2070 rpm.
How the alarm was tested#
- Start the emergency generator.
- Move the fuel injection pump rack by hand to raise the speed.
- The Overspeed alarm comes up on the ECMS-850EH.