Shipboard electric motors: routine maintenance checks and tests

ElectricalPumps

Notes#

Preventive maintenance of shipboard electric motors comes down to daily attention plus a few periodic checks and tests. The best thing I know is an electro-technical officer (ETO) on board who watches the motors every day: small checks on the daily round prevent large repair costs and equipment downtime. This note is general; it is not about a particular motor, maker, model, rating or fault.

My routine checks. These intervals are my own practice, not maker or class requirements:

  • Ball bearings: renew at the interval the maker gives. Check whether the bearing should be the closed or open type. Use bearings from a well-known maker. Keep the motor correctly aligned with the pump.
  • Overhaul: complete overhaul every 5 years. Clean the windings then, and varnish them only if needed.
  • Insulation resistance: megger test 3-4 times a year.
  • Vibration: take readings 3-4 times a year and keep them as reference values for later comparison.
  • Space heater: check that it works.
  • Running condition: watch the running current (amps) and listen for noise.
  • Temperature and ventilation: check how hot the motor body is and make sure there is enough ventilation.
  • Protection: check from time to time that the motor protection trips the motor correctly.

Diagnostic tests that can be used for preventive maintenance:

  • Visual and endoscope inspection
  • Capacitance and tan delta
  • Partial discharge
  • Wedge deflection
  • ELCID
  • Natural frequency test
  • Surge test
  • Motor circuit analysis
  • DC tests
  • Residual life assessment

I don't have intervals or acceptance values for these tests.

What this note doesn't cover: insulation test voltage and minimum megohm values, vibration limits or a standard to judge them (for example ISO 10816), greasing intervals and grease type, temperature limits, how to test the motor protection, and maker service letters or class requirements. I take these values from the maker's manual and the vessel's planned maintenance system.