Log inJoin
Search

Cases

0 rating0 commentsDiesel oil bunkering: tank overflow through a taped vent, engine room fire (Stride)IncidentBoiler · MAN B&W 7S70MC Mk6 · Diesel oil seen dripping from upper ER; no tank high-level alarm recordedGeneral cargo ship alongside at LaPorte, Texas, taking 80 mt of LSMGO into the port and starboard double-bottom DO tanks. The C/E and 3/E ran the bunkering from the ECR, with both fill valves open.…Anonymous · 1 y0 rating0 commentsThermal oil fire from a failing pump bearing, water mist did not work (Pride of Hull)IncidentPumps · Allweiler NTT 80-200 · ER fire alarm, zone "Oil treatment pumps"Ro-ro passenger ferry, outbound in the Humber. Thermal oil (Texatherm 32, winter set point 170 °C) carried heat from the economisers and a boiler. Circulation pump #1 was on duty. The fire panel…Anonymous · 4 y0 rating0 commentsAux boiler explosion: waxy MGO, then fan restart into a gassy furnace (Manhattan Bridge)IncidentBoiler · "" · Aux boiler emergency trip (Furnace flame-eye abnormal)A 13,900 TEU container ship was berthing at Felixstowe in winter. The auxiliary boiler (rotary cup burner) had been on MGO for three days for the ECA. It tripped four times between 17:30 and 19:51.…Anonymous · 8 y