Terasaki PMS: generator will not parallel in auto, "ACB non close"
EL-0011 · Solved · rating 0 · works for 0 engineers · occurred 09 Nov 2022
Source: /cases/el-0011
Symptoms#
- When a generator was put in parallel in automatic mode, the alarm "ACB non close" came up. The breaker did not close and the engine stayed running with no load.
- Frequency and voltage were the same as the bus.
- The synchroscope did not rotate normally. It swung from side to side all the time.
- Both standby generators had the same problem. It started suddenly; nobody had touched the AVR.
- The engine governor is a Woodward UG-8.
Checked#
| Check | Result |
|---|---|
| Fuel pressure, filter differential pressure | Normal, no differential |
| Voltage, generator vs bus | Matched within 0.2 V |
| Manual synchronizing | Breaker closed with no problem (power factor showed lead, other sets lag) |
Diagnosis#
The fault was in the relay between the digital synchronizer and the PLC that passes the synchronizing (breaker close) signal. In manual mode the close signal does not go through this relay. That is why manual synchronizing worked and automatic did not.
Fix#
Replaced the faulty relay.