Log inJoin

Generator will not come off the bus at stop: "Stop failure", reverse power

ElectricalStop failure

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • The undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt.
  • To keep the breaker usable, the UV coil plunger was held in with its mechanical lock.
  • The generator synchronised and went in parallel normally.
  • First stop: load came down slowly to 50 kW, then a "Stop failure" alarm, and the generator took the load back.
  • After reset, second stop: the generator went into reverse power, −90 kW.
Inside the generator ACB: UV coil and the plunger lock (circled)
Inside the generator ACB: UV coil and the plunger lock (circled)

Diagnosis#

On this breaker the opening command and the protection trips work through the UV coil. With the plunger locked, the breaker cannot be opened electrically, so the generator stays on the bus. The locked plunger also blocks the protection trips.

In the same situation the breaker can still be opened by hand with the OFF button on the breaker.

Fix#

Found a spare UV coil and fitted it in place of the burnt one (plunger lock removed).

Result#

The generator synchronises and comes off the bus normally.

Comments · 0

No comments yet.

Sign in to comment, vote and confirm fixes.Sign in