▲0 rating0 commentsHFO transfer pump: start relay chatters, pump will not start in manualTroubleshootingPumpsWhen Start is pressed, relay 4 in the starter crackles and buzzes. The main contactor does not pull in. The main contactor is new. With one output wire of the control circuit disconnected, the pump…Anonymous · 2 y▲0 rating0 commentsTerasaki PMS: generator will not parallel in auto, "ACB non close"TroubleshootingElectrical · Terasaki PMS · ACB non closeWhen a generator was put in parallel in automatic mode, the alarm "ACB non close" came up. The breaker did not close and the engine stayed running with no load. Frequency and voltage were the same as…Anonymous · 4 y▲0 rating0 commentsSteering gear pump motor gets voltage but does not turn or humTroubleshootingSteering GearThe steering gear pump motor did not start. It did not turn and did not even hum. Voltage was present between phases at the motor terminal box.Anonymous · 5 y▲0 rating0 commentsKangrim boiler: "Flame failure" alarm while stopped, will not resetTroubleshootingBoiler · Kangrim · Flame failureFLAME FAILURE alarm came up while the boiler was stopped (not firing). The alarm could not be reset. A restart did not help.Anonymous · 2 y▲0 rating0 commentsKangrim boiler: "Flame failure" at the end of the ignition timeTroubleshootingBoiler · Kangrim · Flame failureComposite boiler. It had run in manual for more than a week. When it was switched to auto, the "Flame failure" alarm came. The burner starts and the flame burns. The alarm comes at the moment the…Anonymous · 5 y▲1 rating0 commentsHyundai HV switchboard: generator VCB tripped, no reset buttonTroubleshootingElectrical · Hyundai HIMAP-BCThe generator engine shut down on lube oil. HIMAP showed reverse power, and the generator VCB (6600 V) tripped. The breaker could not be reset at the breaker. There is no reset button and no handle…Anonymous · 7 mo▲0 rating0 commentsEmergency generator will not crank on batteries that test OKTroubleshootingAuxiliary EngineThe emergency generator did not start on the electric starter, from the remote panel or from the local panel on the engine. The engine turned over once or twice, then stopped cranking. The start…Anonymous · 4 y▲0 rating0 commentsControl room console: lamp test, duty engineer call and phone horn all deadTroubleshootingElectricalSeveral functions of the engine control room console stopped at the same time: Lamp test did not work. Duty engineer call did not work. When the engine room telephone rang, the loud horn in the…Anonymous · 7 y▲0 rating0 commentsMain air compressor will not start, contactor does not pull inTroubleshootingCompressed AirOne main air compressor was opened up for overhaul. Then the other one stopped starting, both in auto and in manual. Pressing Start did nothing.Anonymous · 7 y▲0 rating0 commentsDaihatsu 6DK generator: testing overspeed without a test buttonKnowledgeAuxiliary Engine · Anqing Daihatsu 6DK, Nanjing Chuzheng speed switchThe generator engine has a separate speed switch unit (Nanjing Chuzheng). It has no test button. The settings on its label: Setting Value Low speed 300 rpm Rated speed 720 rpm Overspeed 815 rpm…Anonymous · 6 y▲0 rating0 commentsProvision plant compressor does not stop at pump-down, overcurrent tripTroubleshootingRefrigeration & HVACThe suction line has two low pressure switches: one stops the compressor, the other opens the unloader valve. When all cold room solenoid valves closed and suction pressure fell, the stop switch did…Anonymous · 7 y▲0 rating0 commentsNMF deck crane: no POWER REQUEST after flooding, CPU blinks RUN/STOPTroubleshootingDeck Machinery · NMF crane, Moeller XC-CPU201The cranes were badly flooded: slip rings and control panels. Slip rings and panels were cleaned and dried. The cranes had been without power for 2 days. Cranes 1 and 3 started. On crane 2 the POWER…Anonymous · 3 y▲0 rating0 commentsFire pump 115 kW: main breaker trips at star-delta changeoverTroubleshootingPumpsTwo fire pumps, 115 kW each. One starts normally. The other runs up on star without problems. At the changeover to delta, the main breaker trips. At the changeover, the current goes off the scale of…Anonymous · 6 y▲0 rating0 commentsSiemens LOGO! fuel changeover: program loaded but does not runTroubleshootingAutomation / PLC · Siemens LOGO! 230RC with DM8 230R and AM2 expansion modules · Control failThe automatic HFO/MDO changeover (valves and fuel heating) is controlled by a Siemens LOGO! 230RC with expansion modules. A "Control fail" alarm came up on the fuel page of the control PC. Expansion…Anonymous · 3 y▲0 rating0 commentsThermal oil fire from a failing pump bearing, water mist did not work (Pride of Hull)IncidentPumps · Allweiler NTT 80-200 · ER fire alarm, zone "Oil treatment pumps"Ro-ro passenger ferry, outbound in the Humber. Thermal oil (Texatherm 32, winter set point 170 °C) carried heat from the economisers and a boiler. Circulation pump #1 was on duty. The fire panel…Anonymous · 4 y