Emergency generator breaker closes and opens again at once, no trip
EL-0007 · Solved · rating 0 · works for 0 engineers · occurred 20 Nov 2021
Source: /cases/el-0007
Symptoms#
- The emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode.
- On "close" the breaker clicked and closed. The green "closed" indication was on for a split second, then the breaker opened again.
- No trip and no alarms.
Checked#
| Check | Result |
|---|---|
| Micrologic trip unit | Replaced with a new one — no change |
| Closing spring | Charges normally |
| Supply to the undervoltage release (MN), from a rectifier | 237 V DC (rated 250 V) — taken as within limits |
| Breaker mounting and control terminals | Fixed type (not withdrawable), terminals tight |
| Before the fault | The breaker had worked on load without problems |
Diagnosis#
The fault was not in the emergency generator breaker. The bus tie breaker did not open at blackout: the undervoltage release (MN) inside it had failed. While the bus tie stayed closed, the emergency generator breaker could not stay on the bus.