Emergency generator breaker closes and opens again at once, no trip

ElectricalSchneider Masterpact NT06 H2, Micrologic 5.0 A

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Comments · 0

Symptoms#

  • The emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode.
  • On "close" the breaker clicked and closed. The green "closed" indication was on for a split second, then the breaker opened again.
  • No trip and no alarms.
Emergency generator breaker: Masterpact NT06 H2 with Micrologic 5.0 A
Emergency generator breaker: Masterpact NT06 H2 with Micrologic 5.0 A

Checked#

CheckResult
Micrologic trip unitReplaced with a new one — no change
Closing springCharges normally
Supply to the undervoltage release (MN), from a rectifier237 V DC (rated 250 V) — taken as within limits
Breaker mounting and control terminalsFixed type (not withdrawable), terminals tight
Before the faultThe breaker had worked on load without problems

Diagnosis#

The fault was not in the emergency generator breaker. The bus tie breaker did not open at blackout: the undervoltage release (MN) inside it had failed. While the bus tie stayed closed, the emergency generator breaker could not stay on the bus.