Aalborg thermal oil boiler: no fuel from the nozzle at ignition
EL-0026 · Solved · rating 0 · works for 0 engineers · occurred 04 Jun 2025
Source: /cases/el-0026
Symptoms#
- After a safety alarm test the boiler stopped and did not start again.
- The coil of the recirculation (return) solenoid valve had burnt. It had run hot for a long time: it looked melted and its wiring shorted.
- After a new coil was fitted: spark is visible, but the nozzle sprays nothing and the furnace stays dry. The LAL trips on safety (no flame).
- Fuel is MGO. Inlet and return gauges look normal; return steady at 5 bar.
Checked#
| Check | Result |
|---|---|
| Burner-mounted fuel pump | Replaced, gives 25 bar |
| Both fuel supply pumps | Tried, no change |
| Filter after the pump | Replaced |
| Nozzle solenoid valves | Replaced with new |
| Inlet and return solenoids | New coils; valves cleaned and swapped |
| Atomizer | Replaced three times |
| Solenoid power | Present, all click in the LAL sequence |
| Flow arrows, coil voltage | Correct (220 V nozzle, 110 V inlet/return) |
Diagnosis#
A ball valve was fitted in place of the recirculation solenoid (item 7). Opening and closing it did not change the return pressure, so no fuel was passing through.
- The recirculation solenoid valve was jammed, and this burnt its coil. A new coil alone did not help.
- A "new" spare valve fitted during the search was a used, overhauled one. It clicked when powered but stayed closed.
Fix#
- Overhauled the recirculation solenoid valve until it really worked (five attempts).
- Overhauled the normally open nozzle solenoid valve (item 4) again.
- Refitted the original burner pump and the old atomizer. With the new atomizers the burner would not fire.
Result#
The boiler fires and runs normally.