Boiler burner smokes, and more air makes it worse
EL-0015 · Solved · rating 0 · works for 0 engineers · occurred 16 Aug 2023
Source: /cases/el-0015
Symptoms#
- The boiler was smoking.
- Adding more combustion air made the smoke worse.
- The burner is set to run on the first stage only. The second stage was switched off on the panel.
Diagnosis#
The second-stage fuel solenoid valve clicked open a short time after the burner started, although the second stage was switched off on the panel. The extra fuel from the second stage caused the smoke.
Fix#
Disabled the second stage completely.
Result#
Combustion is back to normal. Why the second-stage solenoid was energised was still being checked.