Log inJoin

Boiler burner smokes, and more air makes it worse

Boiler

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • The boiler was smoking.
  • Adding more combustion air made the smoke worse.
  • The burner is set to run on the first stage only. The second stage was switched off on the panel.

Diagnosis#

The second-stage fuel solenoid valve clicked open a short time after the burner started, although the second stage was switched off on the panel. The extra fuel from the second stage caused the smoke.

Fix#

Disabled the second stage completely.

Result#

Combustion is back to normal. Why the second-stage solenoid was energised was still being checked.

Comments · 0

No comments yet.

Sign in to comment, vote and confirm fixes.Sign in